Page 39 - Enprode Engineering & Construction
P. 39

Power Plant Key

        A. Gas Turbine
        B. Heat Recovery Steam Generator
        C. By-pass Stack & Diverter
        D. Switchgear
        E. Step-Up Transformer
        F. Existing CHP                                                                                       Completed Project





















































        MAIN TECHNICAL PARAMETERS


        Overall Plant Data
        Gross power output ..................................................................................................................... 26 Mwe
        Gross electrical efficiency................................................................................................................... 33%
        Fuel type................................................................................................. Natural gas / Diesel (Dual Fuel)
        Gas Turbine
        Type................................................................................................................................ Siemens SGT-600
        Site rating.................................................................................................................................. 23300 kWe
        Exhaust Gas Flow............................................................................................................................ 459 t/h
        Exhaust Gas Temperature.............................................................................................................. 549 °C
        Heat Recovery Steam Generator
        Type................................................................... Vertical Drum Type Boiler with Supplementary Firing
        Heat Exchangers:
               HP.......................................................................................... Mix Eco, Eco, Boiler, Superheater
               LP........................................................................................................................... Mix Eco, Boiler
        Process Steam
        HP Steam.................................................................................................... 42 bar / 445 °C /100 t/h Max
        LP Steam ...................................................................................................... 6,5 bar / 205 °C / 6 t/h Max
        Operation Modes............................................................................................................ TEG, TEG+SF, FA